Generator Rough Running Range

Units: MW
Mode: Input Only
Multi-band: True
Default Value: 0
Validation Rule: ≥0
Key Property: No
Description: Length of rough running range (must be paired with Rough Running Point)
Detail:

A Generator Rough Running Range is a range of output levels that must be avoided. Typically these apply to hydro generators and are output levels that might cause cavitation in the turbines, PLEXOS allows modelling of rough running ranges on any unit type. Rough Running Point marks the start of a rough running range and Rough Running Range is the length of the range, both properties are in megawatts.

In PLEXOS, rough running ranges are only modelled on single unit generators i.e. these properties will be ignored for multi-unit stations.

The rough running range properties are multi-band, so you can model more than one rough running range on a unit by setting the properties for each range on a different band.

Example:

Generator Property Band Value Units
Gen Units 1 1 -
Gen Max Capacity 1 300 MW
Gen Min Stable Level 1 15 MW
Gen Rough Running Point 1 200 MW
Gen Rough Running Range 1 25 MW
Gen Rough Running Point 2 270 MW
Gen Rough Running Range 2 25 MW