Line Enforce Limits
Units: | - |
Mode: | Input Only |
Multi-band: | False |
Default Value: | 1 |
Validation Rule: | In (0,1,2,3) |
Key Property: | No |
Description: | Controls when flow limits are enforced with regard to Transmission [Constraint Voltage Threshold]. |
Detail: |
Line Enforce Limits can take these values:
- Never (value = 0)
- Line thermal limits are never enforced.
- Voltage (value = 1)
- Line thermal limits are enforced only if the voltage of the line (as defined by Voltage) is at or above the threshold defined by Constraint Voltage Threshold.
- Always (value = 2)
- Line thermal limits are enforced.
- Contingency (value = 3)
- Line thermal limits are enforced only for contingency analysis.
Note: when the line thermal limits are not enforced, the power flow is not bounded and there will be no violation or violation cost.