Line Enforce Limits

Units: -
Mode: Input Only
Multi-band: False
Default Value: 1
Validation Rule: In (0,1,2,3)
Key Property: No
Description: Controls when flow limits are enforced with regard to Transmission [Constraint Voltage Threshold].
Detail:

Line Enforce Limits can take these values:

Never (value = 0)
Line thermal limits are never enforced.
Voltage (value = 1)
Line thermal limits are enforced only if the voltage of the line (as defined by Voltage) is at or above the threshold defined by Constraint Voltage Threshold.
Always (value = 2)
Line thermal limits are enforced.
Contingency (value = 3)
Line thermal limits are enforced only for contingency analysis.

Note: when the line thermal limits are not enforced, the power flow is not bounded and there will be no violation or violation cost.