Zone Capacity Reserves
Units: | MW |
Mode: | Output Only |
Multi-band: | False |
Default Value: | |
Validation Rule: | |
Key Property: | No |
Description: | Capacity reserves (net of Peak Load) |
Detail: |
Zone Capacity Reserves is the megawatt capacity reserve margin. The definition of this property depends on the simulation phase.
- PASA
Capacity Reserves reported by PASA is the capacity margin after allowances for maintenance i.e it is defined as:
Capacity Reserves = Rated Capacity - Peak Load - Discrete Maintenance - Distributed Maintenance- LT Plan
Capacity Reserves reported by LT Plan is defined as:
Capacity Reserves = Firm Generation Capacity + Curtailable Load - Planning Peak Load - Net Capacity Interchange- MT Schedule and ST Schedule
Capacity Reserves reported by MT Schedule and ST Schedule is defined as:
Capacity Reserves = Firm Generation Capacity + Curtailable Load - Peak Load - Net Capacity InterchangeSee also: