Line Resistance

Units:pu
Mode:Input Only
Multi-band:False
Default Value:0
Validation Rule:Any Value
Key Property:No
Description:A measure of the line's opposition to the flow of electric charge

Line Resistance is calculated as: Resistance (pu) = Resistance (actual) x MVA Base / Un^2. It is used to determine the loss in the line: Loss = (Resistance / MVA Base) x (Flow) ². where Un is the rated voltage of the line, expressed in kV (i.e. 220 kV, 400 kV, etc.).

NOTE: Resistance with negative value will be considered as zero. In addition, if the [Resistance/MVA Base] < 0.000001 , loss will be considered as negligible and will not be modeled for this line.