Transformer Screening Mode

Units:-
Mode:Input Only
Multi-band:False
Default Value:1
Validation Rule:In (0,1,2)
Key Property:No
Description:The set of transformers that should be screened for post-contingency flow under screen contingencies

Transformer Screening Mode determines if a transformer's pre/post-contingency flow would be examined.

Never (value = 0)
This transformer's pre/post-contingency flow will not be examined against pre/post-contingency limits under base case and screen contingencies.
Default (value = 1)
This transformer's post-contingency flow will be examined against post-contingency limits under screen contingencies if this line is being monitored under base case.
Always (value = 2)
This transformer's pre/post-contingency flow will be examined against pre/post-contingency limits under base case and screen contingencies.