Flow Control Min Impedance
Units: | pu |
Mode: | Input Only |
Multi-band: | False |
Default Value: | 0 |
Validation Rule: | Any Value |
Key Property: | No |
Description: | Min Impedance |
Detail: |
Flow Control Min Impedance is user specified Impedance limits for DSR, TCSC and MSSR type of devices. The Impedance limitation can be derived as a function of line flow:
FlowFC ≤ - FlowLine x Xmin / (XLine) If FlowLine is positive ( FlowLine >0) FlowFC ≥ - FlowLine x Xmin / (XLine) If FlowLine is negative ( FlowLine <0)Therefore, the Min Impedance input is applied as flow/angle limits and replacing the user input Max Angle.Note that Min Impedance must be smaller than or equal to Max Impedance.
See also:
- Flow Control Type