Flow Control Type
Units: | - |
Mode: | Input Only |
Multi-band: | False |
Default Value: | 0 |
Validation Rule: | In (0,1,2,3,4,5) |
Key Property: | No |
Description: | Flow control type |
Detail: |
Flow Control Type is Flow control type.
- PST (value = 0)
Normal Phase-Shifting Transformer
- DSR (value = 1)
Distributed Series Reactor (DSR) is a saturable reactor, and therefore the maximum inductance of a fleet of units is current-dependent. The angle-flow curve is modeled by using Angle Points and Flow Loading Points.
- DSSC(value = 2)
Distributed Static Series Compensator (DSSC) is modelled as an AC voltage source in series with any given line. The voltage injected is fully variable within certain bounds.
- MSSR(value = 3)
Mechanically-Switched Series Reactor (MSSR) is able to inject discrete levels of inductance to achieve angle shifting between 0 and Max Angle.
- TCSC(value = 4)
Thyristor-Controlled Series Capacitor (TCSC) is modeled as a current-dependent impedance that can be inductive or capacitive.
- SSSC(value = 5)
Static Synchronous Series Compensator (SSSC) is modeled as a variable series voltage source, with allowable angle ranging from Min Angle to Max Angle. Typically only one unit installed per line