Flow Control Min Impedance

Units:pu
Mode:Input Only
Multi-band:False
Default Value:0
Validation Rule:Any Value
Key Property:No
Description:Min Impedance

Flow Control Min Impedance is user specified Impedance limits for DSR, TCSC and MSSR type of devices. The Impedance limitation can be derived as a function of line flow:

FlowFC ≤ - FlowLine x Xmin / (XLine) If FlowLine is positive ( FlowLine >0) FlowFC ≥ - FlowLine x Xmin / (XLine) If FlowLine is negative ( FlowLine <0)

Therefore, the Min Impedance input is applied as flow/angle limits and replacing the user input Max Angle.Note that Min Impedance must be smaller than or equal to Max Impedance.

See also: