Battery Firm Capacity
Units: | MW |
Mode: | Input Only |
Multi-band: | False |
Default Value: | 0 |
Validation Rule: | Any Value |
Key Property: | No |
Description: | Contribution of the battery to capacity reserves |
Detail: |
- Input
Battery Firm Capacity is the contribution of the battery to capacity reserves. By default the capacity provided by each battery unit to regional or zonal capacity reserves requirements is equal to the Max Power, but this can be overridden by defining Firm Capacity directly.
Firm Capacity is used in the calculation of Region (and/or Zone) Capacity Reserves in both PASA and LT Plan. For LT Plan it is the contribution each unit installed/built/retired makes towards any Capacity Requirement in that Region or Zone.
Example
Property | Value | Unit | Band | Date From | Date To | Timeslice | Data File |
---|---|---|---|---|---|---|---|
Units | 100 | - | |||||
Max Power | 1 | MW | |||||
Firm Capacity | 0.08 | MW |
The total installed capacity in this case is 100 × 1MW = 100MW, but the Firm Capacity is only 8% of this, or 8MW.
- Output
Battery Firm Capacity as output is based on the input Firm Capacity if that is defined:
Firm Capacity = Firm Capacity × Unitsotherwise:
Firm Capacity = Installed Capacity