Flow Control Max Voltage

Units: kV
Mode: Input Only
Multi-band: False
Default Value: 0
Validation Rule: Any Value
Key Property: No
Description: Max Voltage
Detail:

Flow Control Max Voltage is user specified voltage limits for SSSC and DSSC type of devices. The voltage limitation can be derived as extra bound for Flow Control phase angle:

θFC ≤ (Vmax / Vnom) x cos(θ1 - θ2)/2

Assumption is introduced here to adopt the nonlinear equation to linear programming:

Assume: cos(θ1 - θ2)/2 = 1

Therefore, the Max Voltage input is applied as angle limits and replacing the user input Max Angle:

θFC ≤ (Vmax / Vnom)

Please note that Vnom is the nominated line voltage, which is read from Node Voltage. If Node Voltage is not defined, the Flow Control Max Voltage will be ignored.