Flow Control Min Voltage

Units: kV
Mode: Input Only
Multi-band: False
Default Value: 0
Validation Rule: Any Value
Key Property: No
Description: Min Voltage
Detail:

Flow Control Min Voltage is user specified voltage limits for SSSC and DSSC type of devices. The voltage limitation can be derived as extra bound for Flow Control phase angle:

θFC ≥ (Vmin / Vnom) x cos(θ1 - θ2)/2

Assumption is introduced here to adopt the nonlinear equation to linear programming:

Assume: cos(θ1 - θ2)/2 = 1

Therefore, the Min Voltage input is applied as angle limits and replacing the user input Min Angle:

θFC ≥ (Vmin / Vnom)

Please note that Vnom is the nominated line voltage, which is read from Node Voltage. If Node Voltage is not defined, the Flow Control Min Voltage will be ignored.