Outage Scale Method Column

This column offers various options for scaling forced or maintenance outages across segments of a unit.

To illustrate the various options, assume a unit with 100 MW of capacity, a Min Capacity of 30% (or 30 MW), 7 other segments defined at 10 MW each and a Forced Outage (FOR) of 10%.

In the example unit, segment 8 (top) would have 0 capability, segments 2-7 would all have 10 MW, and the Minimum Segment would have 30 MW. If it had been an FOR of 15%, then, again, segment 8 (top) would have 0 capability, segment 7 (next) would have 5 MW capability, segments 2-6 would all have 10 MW, and the min segment would still have 30 MW.

In the example unit, 10 MW of reduction in capability is needed (FOR of 10%), but that is applied evenly to segments 2-8. 10 MW / 7 remaining segments = 1.429 MW/segment. Now, segments 2-8 would have 10 – 1.429 = 8.571 MW, and the min segment would still have 30 MW.

In the example unit, segments 2-8 would have 10 * (1 – 0.10) = 9 MW, and the min segment would have 30 * (1 – 0.10) = 27 MW.

A blank, null value, or missing column will default to scale outages proportionally across each segment of the unit.

 

This is especially relevant when using multiple segments defined by the Heat Rate Definitions table.

 

 Input Tables

 Resources Table

 Outage Scale Method Column


For further assistance, please contact Aurora Support.

Copyright© 1997-2024 Energy Exemplar LLC. All rights reserved.