Column Type = Text
Used to define the type of diagnostic records to be reported. These values are not case sensitive.
Load Source - Output will be created in the NodalDiagLoadSource table describing the sources of loading for the specified transmission element for the current hour solution. A list will be created for the set of induced flows on the requested element having the highest absolute values. The number of values reported in the list will be limited by NVal Reported. The reported list will contain the injection buses, injection amounts, shift factors, induced flows, an marginal cost of generation at the associated injection bus.
If the study is a security constrained (SCOPF) run, i.e. a Contingency table is included in the study, additional output will be created describing the flow transfer that would occur for each contingency element to the requested element if the contingency were to happen.
Shift Factor - Output will be created in the NodalDiagShiftFactor table listing a set of shift factors having the highest absolute values for the requested element. The number of values reported will be limited by NVal Reported.
LODF - Output will be created in the NodalDiagLODF table for each LODF for each contingent element in each contingency to the requested transmission element. This option will only be recognized in an SCOPF study.
Contingency Flow - Output will be created for the requested elements and time period in the NodalDiagContingencyFlow table reporting the flow on a branch or a corridor that would occur for each given contingency absent re-dispatch. This report is useful to identify contingency-driven overloads and more generally the significance of contingencies on the SCOPF solution
Contingency Monitored Flow - This type is the same as the Contingency Flow type above, except that it only report records for contingencies in which the branch/corridor is monitored. Output will be created for the requested elements and time period in the NodalDiagContingencyFlow table. This option is useful for reducing output table size.
NOTE: The Shift Factor and LODF reports are network dependent and thus will only change when branch outages change. Therefore there is no point in enabling Shift Factor and LODF reporting more than once during each unique branch outage configuration as determined by the Branch Outage table. The Load Source report is impacted by changes in generation and/or demand profiles. The Load Source report will contain different data for each hour reported regardless of branch outages.
Report Type Column
For further assistance, please contact Aurora Support.