Generator Firm Capacity

Units:MW
Mode:Input/Output
Multi-band:True
Default Value:0
Validation Rule:Any Value
Key Property:No
Description:Contribution of the generator to capacity reserves
Input

By default the capacity provided by each generating unit to regional or zonal capacity reserves requirements is determined by the Generator Firm Capacity Basis setting, which defaults to the Max Capacity, but this can be overridden by defining Firm Capacity directly.

Firm Capacity is used in the calculation of Region (and/or Zone) Capacity Reserves in both PASA and LT Plan. For LT Plan it is the contribution each unit installed/built/retired makes towards any Capacity Requirement in that Region or Zone.

Example

Property Value Unit Band Date From Date To Timeslice Data File
Units 100 -




Max Capacity 1 MW




Rating 0 MW



wind.csv
Firm Capacity 0.08 MW





This is an example input for a wind generator. The total installed capacity in this case is 100 × 1MW = 100MW, but the Firm Capacity is only 8% of this, or 8MW.

Note: For the Firm Capacity to work, the Max Capacity must be defined as a non-zero value.

Output

Generator Firm Capacity as output is based on the input Firm Capacity if that is defined:

Firm Capacity = Firm Capacity × Units

otherwise:

Firm Capacity = Installed Capacity or Rated Capacity depending on Firm Capacity Basis

Multi-band

Firm Capacity can also be modeled with multi-bands. Each consecutive band shows the additional Firm Capacity provided by building additional units in Firm Capacity Unit Count.

Example


In the above example, the first 2 units built have 25 Firm Capacity each (corresponding to Band 1). The next 3 units built have 20 Firm Capacity each (corresponding to Band 2). Bands 3 and 4 follow likewise.

Note: Any units built beyond what is specified in the Unit Count of the final Band each have the Firm Capacity of the final Band.