Generator Ramp Flexibility Down

Units:MW
Mode:Output Only
Multi-band:False
Default Value:
Validation Rule:
Key Property:No
Description:Amount of unused ramp down capability

Generator Ramp Flexibility Down is the amount of unused ramp down capability given the current commitment state:

Ramp Flexibility Downt = MIN ( Generationt-1 - Min Stable Level × Units Generatingt-1 - Ramp Downt , Max Ramp Down × Units Generatingt-1 × time - Ramp Downt )

Other technical constraints are also included, such as the start and shutdown profiles. When the generator is starting or shutting down, it cannot provide any additional ramp up/down capacity.

See also: